Akuvox General || A092/A094 12-Volt Output Wiring

Akuvox General || A092/A094 12-Volt Output Wiring

A092 / A094 12-Volt Output Wiring

For use when installing an Access Control System without utilizing an External Power Supply to provide 12 Volts to devices

 

 

 

Using a single Jumper wire;
Connect the 12V_OUT to the RELAY_COM port.

 

 

 

 

For Strike Wiring:

Connect Positive wire to the RELAY_NO port (Normally Open)
Connect Negative wire to the GND port (Ground)
(Note: Some strikes will not have wires labeled for Positive/Negative.)

 


 

For Maglock Wiring:

Connect the Positive wire to the RELAY_NC port (Normally Closed)
Connect the Negative wire to the GND port (Ground)

 

 

The 12V Output must be Enabled on the web interface.

Using a PC connected to the same network, log in using the IP address of the device.

 

Username: admin

Password: admin

 

Navigate to the Access Control tab on the left and select Relay.

Use the drop-down menu under 12V Power Output section to enable the output for the desired port.

Click Submit.