Akuvox General || Maglock & Exit Button Wiring for A02S

Akuvox General || Maglock & Exit Button Wiring for A02S

Maglock & Exit Button to A02S Wiring Diagram

 

 

Maglock Wiring:

Connect the Positive wire from Maglock to the RELAY_NC port.

Connect the Positive wire from Power Supply to the RELAY_COM port.

Connect both Negative wires together from Maglock & Power Supply.

 

Exit Button Wiring:

Connect the Normally Open (NO) wire from Exit Button to the RELAY_IN1 port.

Connect the Common (COM) wire from Exit Button to the RELAY_COM port.

 

Log in to the web interface of the device using the IP address from a web       browser.

*** Note: Your computer must be connected to the same network as the device.***

It is recommended that you use the Akuvox IP Scanner tool from the knowledge base website.

( www.knowledge.akuvox.com/docs/akuvox-ip-scanner )

 

 

Web Interface Login

Username: admin

Password: admin

 

Select the ‘Access Control’ tab on the left hand side of the screen.
Then select the ‘Input’ tab.
Checkmark the box to Enable
the input.

 

Use the Drop-down Menu next to Execute Relay, and choose the desired relay to be activated.

 

Click Submit at the bottom of the page.

    • Related Articles

    • Akuvox General || Maglock & Exit Button Wiring

      Maglock & Exit Button Wiring Using R20K model as an example: Log in to the web interface of the device’s IP address from a web browser. Note: To find the IP address of your device, your computer must be connected to the same network. It is ...
    • Akuvox General || R20A Wiring Diagram Maglock & Exit Button

      Connect 12-Volt Positive from Power Supply to the COM (Common) port on the back of the R20. Connect Positive Wire from the Maglock to the NC (Normally Closed) port. Connect both Negative (Ground) wires together from the Maglock and Power Supply. For ...
    • Akuvox General || Exit Button AC-05 Wiring

      Exit Button AC-05 Connecting to an Akuvox R20A Model door phone as an example. Connect the Orange wire (N/O) from the AC-05 to the 'Door A' input port. Connect the Yellow wire (COM) from the AC-05 to the 'GND' port. The AC-05 Exit button is powered ...
    • Akuvox Local || Akuvox Door Lock Wiring Diagram

      Akuvox Door Lock Wiring Diagram Note: 1. Akuvox integrates circuit protection onto the main board, so you can directly connect Door Strike to Akuvox door phone. 2. When installing a Akuvox door phone at a building without an access control system, ...
    • Akuvox General || A092/A094 12-Volt Output Wiring

      A092 / A094 12-Volt Output Wiring For use when installing an Access Control System without utilizing an External Power Supply to provide 12 Volts to devices Using a single Jumper wire; Connect the 12V_OUT to the RELAY_COM port. For Strike Wiring: ...