Maglock & Exit Button to A02S Wiring Diagram
Maglock Wiring:
Connect the Positive wire from Maglock to the RELAY_NC port.
Connect the Positive wire from Power Supply to the RELAY_COM port.
Connect both Negative wires together from Maglock & Power Supply.
Exit Button Wiring:
Connect the Normally Open (NO) wire from Exit Button to the RELAY_IN1 port.
Connect the Common (COM) wire from Exit Button to the RELAY_COM port.
Log in to the web interface of the device using the IP address from a web browser.
*** Note: Your computer must be connected to the same network as the device.***
It is recommended that you use the Akuvox IP Scanner tool from the knowledge base website.
( www.knowledge.akuvox.com/docs/akuvox-ip-scanner )
Web Interface Login
Username: admin
Password: admin
Select the ‘Access Control’ tab on the left hand side of the screen.
Then select the ‘Input’ tab.
Checkmark the box to Enable the input.
Use the Drop-down Menu next to Execute Relay, and choose the desired relay to be activated.
Click Submit at the bottom of the page.